1Instruction ManualHI 8001 & HI 8002Panel-mounted and Wall-mountedFertigation ControllersManufacturers since 1978These Instruments are inComplianc
103.3 FERTILIZATION CONTROLFertigation Controller can use up to 4 fertilizer tanks.Each irrigation program can specify the percentage for each type of
11AGES). For each individual sector’s pH average see panel C 24 (SECTORAVERAGES). All pH averages can be deleted manually or at specified time ofday u
13opening and closing of a valve through which a neutral solution is circulated.The amount of neutral solution added is relative to the opening of the
14can compensate for changes in the process variable (measurement) and is par-ticularly good for slowly moving processes. When a change occurs in the
15- To erase all statistics, use panel S 61 (ERASE STATISTICS). Statistics indi-cates pH and conductivity averages for all irrigation programs and sec
163.10 LOGGING FUNCTIONSThe Fertigation Controller has the capability to log the most important occurredevents and values of different parameters that
174 USER INTERFACEThe Fertigation Controller’s user interface consists of a 4 x 20 character LCDand a 23-key keyboard.Keyboard structure.4.1 OPERATING
18different controller entities (programs, sectors, fertilizers etc.) within the samepanel.- LEFT and RIGHT ARROWS KEYS can be used to move the cursor
19- LEFT, RIGHT arrow keys allow navigation within the currently focuseddata object. If the cursor exceeds the boundaries of the data object then thef
2Dear Customer,Thank you for choosing a Hanna Product. Please read this instructionmanual carefully before using the instrument.This manual will provi
204.2 PANEL BROWSING METHODSIn consulting mode, two browsing methods are available to view each of the 62panels (screens) of the Fertigation Controlle
2111 SOL RAD EXTENS 40 PH CONTROL12 MAN CORRECTION 41 COND CONTROL13 TOTAL CORRECTION 42 CORRECTIONS14 SECTOR STATE 43 SOLAR RAD IRRIG15 - 44 -16 FER
225 PANEL DESCRIPTION5.1 GENERAL CONSULTINGThe following panels C 01 through C 29 are for the general consulting ofcontroller settings and current m
23Although access to the controllers features are denied, the functionality of thecontroller is not directly effected if a password authentication seq
24NOTE:- If the user is logged in and the operational mode is CONSULTING MODE,this panel can be accessed anytime and from any panel using the HOME
255.2.1 PROGRAM STATE – C 03PROG 08 ACTIVEStarted by Solar RadRepeat 02/05 13:15PROGRAM STATE C03The purpose of this panel is to allow the user
26REMINDER: In CONSULTING MODE the ESC key can be used as a short-cut key to access this panel from any panel.5.2.2 PH STATE – C 04Prog 08 Ref=06.4
27and is not program specific.S in = Real time value of EC input sensor. This is an option sensor input tomeasure the conductivity of the incoming wat
28DayIndicates if the selected program is set to run on a daily schedule.PeriodIndicates if the selected program is set to run on a yearly schedule.Sy
29This panel displays the current irrigation state of the indexed program. Time orvolume can control irrigation and the above panel displays the set v
35.4 Alarms Consulting ... 375.5 Log Consulting ...
305.2.9 MAN CORRECTION – C 12Prog 08 +015% +00:05:55 13:15MAN CORRECTION C12This panel displays how much the programmed irrigation parameters
315.2.11 SECTOR STATE – C 14Prog 08 Sect 21/21Set 00:10:30+009:45Done 00:03:10 13:15SECTOR STATE C14This panel displays the state of each secto
32This panel displays the set and current amount of fertilizer used for a specificprogram. The Fertigation Controller controls the dosing of 4 fertil
33PauseThe set pause time value for the indexed agitator of the selected program.System clockNOTE: The agitator’s working time values can be specified
345.3 STATISTICS CONSULTING5.3.1 TOTAL ACCUMUL – C 19From: 09-26 13:37;120007654L 13:15TOTAL ACCUMUL C19This panel provides a total
355.3.3 SECTOR ACCUMUL – C 21From: 09-26 13:37;12000:00:17 Sect 01/01 13:15SECTOR ACCUMUL C21This panel provides a total (in time or v
365.3.5 PROGRAM AVERAGES – C 23From: 09-26 13:37;1205.3pH Prog 0106.7mS 13:15PROGRAM AVERAGES C23This panel provides a pH & EC avera
375.4 ALARMS CONSULTING5.4.1 ACTIVE ALARMS – C 25Low level fert: 4ACTIVE Alarm26-12 14:36:22 13:15ALARM 02/07 C25This displays the active alarms
38pressed the Fertigation Controller will search for the logged data. If no data isfound the panel is shifted to C 28 (LOG) and “no records found” is
39SET key or via panel S 59 (SET LOG LEVELS). The UP and DOWN arrow keysare available to move between log records in a “select previous/next” manner.T
41 THEORY OF FUNCTIONIrrigation is one of the most important operation in agriculture. With properirrigation the quality and quantity of crops can be
405.7 PROGRAM SETTINGS5.7.1 ACTIVE TIMETABLE – S 31Between Prog 07Date: 01-04 31-10Time: 07:00 23:00ACTIVE TIMETABLE S31This panel allows the u
41(for more details see Section 3.1 and Appendix 3):Work dayThe number of consecutive workdays.Program NumberReflects the selected program (can be sel
425.7.4 START CONDITIONS – S 34Time cond y Prog 07Solar rad NExt tank: -- Link 02START CONDITION S34Using this panel we can set up how a particular p
43allows the setting of the following parameters:Program NumberReflects the selected program (can be selected only inside panel C 03). SeeSection 5.2.
44mode, see panel S 53 (IRRIG CTRL MODE). The program number indexes thispanel (for more details see Section 3.1 and Appendix 3). This panel display
455.7.9 SET FERTILIZERS – S 39 Prog 07Fer1=020% Fer2=055%Fer3=060% Fer4=040%SET FERTILIZERS S39The fertilizer dosing is controlled b
46Alarm thresholdSelectable pH control alarm threshold represents the time interval (mea-sured in the Fertigation Controller’s control cycles) conside
47fertilization process. The program number indexes this panel. This panel displaysand allows the setting of the following parameters:ManualThe selec
48program. If “Work” and “Pause” are set the agitator will function intermittentlyrelative to the time settings. In this panel the agitator number is
495.8 MANUAL COMMANDS5.8.1 MANUAL START – S 47Active program: 03Start program: -- ?PROG MAN START S47Each program can be manually started using thi
52 GENERAL DESCRIPTIONThe Fertigation Controller is a micro-processor-based system used in fertiliza-tion and irrigation control for greenhouses or op
50Y (yes) can be entered next to the selected condition to change the controllerstate. Only the Y (yes) key will have effect in activating the appropr
51Ctrl in Pre / PostPress Y (yes) then ENTER to control pH prior and after irrigation.Use acid in pHCtrlPress Y (yes) or N (no) then ENTER to control
525.9.4 CALIBRATE SENSORS – S 54 Channel: 01Now: 02.3 Ref: 02.5Status: First StageCALIBRATE SENSOR S54The sensor calibration procedure consist
53SensNr = The selectable number of pH sensors in the system (1 to 2).SensNr = The selectable number of EC sensors in the system (1 to 3).SDifThe maxi
54ECkFactory amplification setting for EC control.ECTiIntegral constant for EC control. Setting the value to 99.9 minutes effec-tively disables the in
55corded and can be inspected at the same time. Alarm events are stored regard-less of log level and can be inspected using panel C 27 (ANOMALY). Pa
565.9.11 ERASE STATISTICS – S 61 Erase all: - On overflow: YDaily at hour: 00:01ERASE STATISTICS S61With this panel it is possible to erase stored
576 CALIBRATION PROCEDURES6.1 SENSOR CALIBRATION PROCEDUREThe purpose of calibrating the Sensor’s used in conjunction with the FertigationController i
586.2 PID TUNING PROCEDUREFor the PID controller, we have three working modes:1. With PID regulation algorithm (Proportional, Integrative and Derivati
596.2.1 PID TUNING PROCEDUREDue to the fact that the pH and EC controls function with minimal error at thecontrol output value, the PID controller mus
63 FUNCTION DESCRIPTIONIn this chapter the main functions of the Fertigation Controller are presented. Fora better understanding see the typical insta
60A. NECESSARY STEPS FOR TUNING THE PID CONTROLLER FOR PH AD-JUSTMENT1. The pH of the water source used for irrigation is measured. When this value is
6110. At the end of the program consult the log table. Write down in a table thevalues for the pH sensor and the time when the reading was done (see S
62- Total number of sectors = 1- Irrigation time = 15 minute2. Go to panel S 38 (SET SECTORS) and check the above settings. If they aredifferent adjus
63NOTE: The period of time for Irrigation time (15 minute default) - panel S 37(PRE/POST IRRIG) - can be modified (increased or decreased), if theproc
64- The control function remains constant; however, a steady state offset ispresent meaning that the set point is never completely maintained.4. INTEG
65sensor #1) is outside of the allowable dead band determined by the specified pHReference value together with the pH min and pH max offset limits. Th
668 TROUBLE SHOOTING GUIDETHE CONTROLLER DOES NOT FUNCTIONCheck to insure that the proper voltage is applied to the controller. After con-necting the
67occurred that may not be correctable by the type and amount of acid (or base)being used. If the problem persists after checking the process pH and a
689 ELECTRICAL DIAGRAMS
7- The accumulated solar radiation starting level value is used as a thresholdvalue for the accumulated solar radiation. When the accumulated solarrad
71POWERBOARDEXTENSIONBOARDMAINBOARD
72APPENDIX 1- KEYBOARD OPERATING MODESCONSULTING MODE:- arrow keys can be used to navigate inside the currently focused object- ESC key can be used as
73APPENDIX 2 - OUTLET ASSIGNMENT TABLEOUTLET NUMBER ASSIGNED ELEMENT08 Filter1 35 SECTOR VALVE 1209 Filter2 36 SECTOR VALVE 1310 pH 37 SECTOR VALVE 14
74APPENDIX 3 - GRAPHICAL EXPLANATION
75
76
77APPENDIX 4 - LIST OF PANELSGeneral InfoWORK Anomalies 00Prog 08 06.4pHSect 07 02.1mS 13:15GENERAL INFO C01Active Program: 0406.3pH 1200W/m2
78Prog 08 Time Y Day Y Period Y 13:15WORK TIME COND C08Prog 08 Priority 05Conflict Programs 02 13:15PRIOR & CONFLICT
79Prog 02 Fert 02 Set 40%Current 20% 13:15FERTILIZ STATE C16Prog 08 Agitator 01Work 00:03 WORKPause 00:02 13:15AGITATOR STATE C1
8SOLAR RADIATION FACTOR:- This option can be set using panel S 42 (CORRECTIONS). This factoraffects the irrigation time or volume extension in accorda
80Prog 07Repeats 04 Pause 00:30:00PROGRAM REPEATS S36 Prog 07 PreIrrig: 000:00:05PostIrrig: 000:00:05PRE/POST IRRIG S37Valve 05 Pr
81Pre 00:33 Prog 08Work 00:10Pause 00:05SET AGITATORS S45Link 05 Filter 01Clean on alarm: YClean time: 01:01:02FILTERS CTRL S46Controlle
82Ctrl on pH alarm: YIrrig on pH alarm: Y Ctrl on EC alarm: YALARM BEHAVIOR S52Volume control: N Time control: YIRRIG CTRL MODE S53 Channel: 01N
83Disable password: NNew password: ---SET PASSWORD S60Statistics ConsultingFrom: 09-26 13:37;120007654L 13:15TOTAL ACCUMUL C19Fro
84Controller LoggingExt state:ACTIVEProg State changed.18-08 15:05:30 15:05Log 0012 Lev 03 C28Manual CommandsActive program: 03Start program: -- ?PRO
85APPENDIX 5 - INSTALLATION BLOCK DIAGRAM
86
87Recommendations for userBefore using this product, make sure that it is entirely suitable for the environment inwhich it is used.Operation of this i
88www.hannainst.comMAN800107/03
9sectors using one of the following ways:- Manually- Every day at specified hour- Automatically when the accumulations counter value overflows3.2 COND