1716
If M1= 3 then S1+D1
HA;
If M1= 4 then S1-D1
LA;
If M2= 1 then S2-H2
LA;
If M2= 2 then S2+H2
HA;
If M2= 3 then S2+D2
HA;
If M2= 4 then S2-D2
LA;
If M1= 1 and M2 = 2
then S1-H1
S2+H2, S2LA, HAS1;
If M1 = 2 and M2 = 1
then S2-H2
S1+H1, S1LA, HAS2;
If M1 = 3 and M2 = 2
then S1
S2+H2, S2LA, HAS1+D1;
If M1 = 2 and M2 = 3
then S1+H1
S2, S1LA, HAS2+D2;
If M1 = 4 and M2 = 1
then S1
S2–H2, S1–D1LA, HAS2;
If M1 = 1 and M2 = 4
then S1–H1
S2, S2–D2LA, HAS1;
If M1 = 3 and M2 = 4
then S1
S2, S2–D2LA, HAS1+D1;
If M1 = 4 and M2 = 3
then S2
S1, S1–D1LA, HAS2+D2;
where the minimum deviation (D1 or D2) is 0.5% of the maxi-
mum range value.
Note When a wrong setup value is confirmed,
the controller does not skip to the next setup
item but remains in the current item dis-
playing a flashing “ERROR” indicator un-
til the parameter value is changed by the
user (the same is also true for the setup code selection).
Note In some circumstances, the user cannot succeed in setting a
parameter to a desired value if the related parameters are not
changed beforehand; e.g. to set a EC high setpoint to 10.0
mS the high alarm must be set to a value greater than 10.0
mS first.
Code Valid Values Default PW
60 Current day 01 to 31 from RTC no
61 Current month 01 to 12 from RTC no
62 Current year 1998 to 9999 from RTC no
63 Current time 00:00 to 23:59 from RTC no
71 Baud rate (RS485) 1200, 2400, 4800, 9600 9600 no
72 Cleaning timer 0 to 19999 days 0 no
73 Initial cleaning day 01 to 31 01 no
74 Initial cleaning month 01 to 12 01 no
75 Initial cleaning year 1998 to 9999 1998 no
76 Initial cleaning time 00:00 to 23:59 00:00 no
77 Cleaning ON interval 0 to 19999 minutes 0 no
90 Display selftest 0: off 0 yes
1: on
91 Keyboard selftest 0: off 0 yes
1: on
92 EEPROM selftest 0: off 0 yes
1: on
93 Relays and LEDs selftest 0: off 0 yes
1: on
94 Watchdog selftest 0: off 0 yes
1: on
99 Unlock password 0000 to 9999 0000 yes
Note The process controller automatically checks to ensure that
the entered data matches other related variables. If a wrong
configuration is entered, “ERROR” blinks on the LCD to prompt
the user. The correct configurations are the following:
If M1=/ 0 then S1
HA, S1LA;
If M2=/ 0 then S2
HA, S2LA;
If M1= 1 then S1-H1
LA;
If M1= 2 then S1+H1
HA;